Structure of KMB <Closed> type Cooling Tower


 Design concept-wise, the closed cooling tower is the opposite of the open type in the sense
that circulating water never contacts ambient air during cooling process. There are two independent
sources of water used for the closed type tower : Circulating water and spray water.

Circulating water runs only inside a totally enclosed copper tube while spray water runs down through.
infill. In this system, spray water cools circulating water running inside the copper tube circuit without
contacting with each other directly.

In this way water never gets concentrated due to the fact that no evaporation takes place in the tube.
Based on this fact, the equipment such as chiller is totally protected against scale, and time & cost for
maintenance can be minimized.

In the region under low W.B. temperature (about 8℃), closed-type cooling tower can be connected to
main cooling equipment directly to function as “COLD WATER GENERATOR” such as chiller.
This system is called “free-cooling” and it greatly contributes to energy-saving.

Heat exchanger : (Coil & fillings) Seamless phosphorus dioxide copper tube is used for the circuit, and the filling"
 pieces are loaded at each individual stage to maximize cooling efficiencies.

For Fan unit, Lower basin, Internal body and Framework, refer to page 1 for detail.